Model 493.73 HPU Interface Board
MTS FlexTest® Models 40/60/100/200 Controller Hardware Digital I/O and Transition Boards
241
J24 E-Stop Input Connections for the Model 493.73 HPU Interface Board
Connector J24 E-STOP In provides an input for an external emergency stop
switch.
Note Emergency stop inputs are part of a controller-wide E-Stop system.
Cable specifications To maintain EMC compliance, 24 E-STOP In cables must comply with the
following specifications:
Connector —15-contact, type D, male EMI connector.
Backshell–EMI metallized plastic or metal.
Cable–24 AWG 4-connector with overall braided shield connected to
metallized plastic backshell at the chassis and to ground at the emergency
stop station.
Jumper plug required If connector J24 is not used, you must install a jumper plug to maintain the
integrity of the interlocks. Use jumper plug part number 039-713-201 or
jumper pins: 5 and 7; 8 and 13.
SERVICE
493.73
HPU
J29
E-STOP OUT
J24
E-STOP IN
J25 HPU
J54
SYS D I/O
+24 V
E-Stop
Out Relay
E-Stop
493.73 HPU Board
J24
E-STOP IN
13
8
7
5
E-Stop
Controller
Signal
J24
E-STOP IN
Zobrazit stránku 240
1 2 ... 236 237 238 239 240 241 242 243 244 245 246 ... 343 344